تسجيل الدخول
تسجيل جديد
الجمعة - رجب 6, 1447
مسجل لدى هيئة الحكومة الرقمية برقم:
20250728714
عن تيقظ
بحث عن منتج
تقديم بلاغ
أسئلة شائعة
تواصل معنا
EN
SA-31-07-25-983
التفاصيل
الرقم المرجعي
الشركة الصانعة
اسم الجهاز الطبي
Philips Azurion and Allura with 1 Phase UPS
الأجهزة المتأثرة
Please refer to the attachment.
الممثل المعتمد
Philips Healthcare Saudi Arabia Ltd
سبب المشكلة
Philips has become aware of a potential safety issue with Philips Azurion and Allura systems configured with a 1 Phase Uninterruptible Power Supply (UPS). Philips has identified that some internal components of the 1 Phase UPS may fail. When this occurs, there will be a complete loss of power to the system, causing the system to shut down and/or not start up. The 1 Phase UPS system may fail without warning and prior to any mains power failure.
الإجراء التصحيحي
Affected systems may continue to be used in accordance with their Instructions for Use (IFU). Customers / users should establish an emergency protocol prior to all applicable diagnostics, interventional and minimally invasive procedures to manage the situation should they experience the issue during a procedure. Philips will bypass the 1 Phase UPS in the affected systems. This will render the 1 Phase UPS inactive, preventing the occurrence of the above-described issue. Not having the 1 Phase UPS connected will not affect system usage during normal operation. Once the 1 Phase UPS is bypassed, controlled shutdown and data backup in the event of a hospital mains power interruption will no longer be available, which may cause the last acquired run to be lost when the power failure occurs during the acquisition or shortly after the run was acquired. Data loss from the last run on Azurion systems is not expected, as these systems are equipped with solid state drives (SSD). Philips will contact all affected customers to schedule the execution of this activity. Manufacturer action: Instructions and Correction
المرفقات
عودة للقائمة